1.BASIC CONFIGURATION AND GENERAL SPECIFICATION
What is receiving panel
Receiving panel plays a role of generating alarms by directly receiving signals generated
by detector or manual control panel or manual actuator.
Major functions of the product
1) Adopt high performance precision microprocessor in the product.
2) Implement a stable system by using processors and relays.
3) Install built-in auxiliary power supply (Ni-Cd Battery) which will automatically kick
immediately when power failure occurs.
4) When the system is actuated by detectors (A&B, A&C, or B&C),by pressure switch, or manually,
the contacts interlocked with the system will be activated(No voltage dry contact)
5) Manage main / auxiliary power supply by adopting a precision A/D converter in auxiliary
power monitoring circuit.
6) When the system is actuated by detector (A, B, or C), externally or manually, it is possible
to save the time of a fire, which can be confirmed via FND.
7) Check the status of built-in auxiliary power supply with an indicator lamp (Normal/Low)
which will turn on when the power level is less than 85% of the supplied voltage.
(Supplied voltage: DC24V, LED lamp starting voltage: DC20.4V)
8) Possible to maintain / repair by disassembling power supply part and terminal connection part.
General specification
1
※Options:When a detector circuit (A, B, or C) is activated, if another detector is not activated within 45 seconds, then the system will be automatically recovered
1) Model : DSCP-1
2) Type approval no : Su 10-22 / Type P Class 2 Complex Receiving Panel
3) Type : AC220V, DC24V, window-type, electronic relay, smoke control system (CO2, halides)
extinguishing system
4) Rated voltage : AC220V / 60Hz (Auxiliary power supply: Ni-Cd Battery DC24V/600mAh)
5) No. of circuit : 1
6) Material of cabinet : Steel 1.2t / Cream-colored powder coating (EK 427K)
7) Alarm : Main bell, sectional bell, buzzer, siren, voice alarm
8) Display : LED lamp (Light emitting diode)
9) Discharge timer : Use FND (digit display)
10) External connection device : main bell, sectional bell, detector, manual control panel,
discharge lamp, siren, solenoid valve, pressure switch
11) Interlocking of auxiliary receiving panel : If an output is occurred by a detector (A, B, or C),
or manual actuation, or gas release, then the system can be used by interlocking with no
voltage dry contact
12) Operating temperature : -10 C ~ 50 C
13) Relative humidity : RH 10% ~ 90% (With no condensation)
14) Cabinet dimension : 250mm x 360mm x 85mm